1 FUNCTIONS
1.1 BACnet Object Function
107
1
3. Click the [Detail] button of an ObjectID to set the details of a schedule.
4. Click the [Add] button of "ListOfObjectPropertyReferences".
5. Set the following items.
6. Click the [Update] button.
When setting multiple properties, all the data types of the property of the object type to be set should be the same.
For example, the following properties cannot be set together because the data type of each property is different.
• PresentValue property of BinaryOutput object (BinaryPV/Enumerated type)
• PresentValue property of AnalogOutput object (REAL type)
Item Description
Device When setting the scheduled operation of another BACnet device, select the "Specify Device" checkbox and enter
the instance number of the device.
ObjectID Select the ObjectType of an object which contains the property for scheduled operation, and enter an instance
number.
PropertyID Select a property for a scheduled operation.
ArrayIndex When the property for a scheduled operation is ARRAY type, select this item and enter the index number of the
property to be controlled.