1 FUNCTIONS
1.8 Event Interaction Function
153
1
3. Set the following items, and click the [Add] button.
*1 For the method to assign multiple data blocks in a batch, refer to the following section.
Page 214 Assigning data blocks using a CSV file
4. Click the [Detail] button.
5. Check the buffer memory address.
Create a program to read Event notification data by referring to the format of access blocks for Event interaction. Replace the
offset +0 in the format of access blocks for Event interaction with the buffer memory address displayed with a configuration
function. (Page 295 Format of access blocks for Event interaction)
6. When the CONTROL of an access block for Event interaction is '1', read Event notification data from the access block for
Event interaction using a program.
For the operation of a BACnet module, refer to the following section.
Page 155 Operation of a BACnet module
Item Description
DeviceInstanceNo Specify the instance number of the send source device of Event notifications.
ObjectID Select the ObjectType of the send source object of Event notifications, and enter an instance number.
BufferMemoryAddress Specify the start buffer memory address of an access block for Event interaction
*1
.
Specify an even number within the range of 256 to 32767 (100h to 7FFFh).
To specify a buffer memory address in hexadecimal, add 'h' at the end of it.
When '0' is specified to the buffer memory address, the data blocks are automatically assigned to the free space in the
buffer memory.