1 FUNCTIONS
1.12 Configuration Function
■ To set the change amount of a value to send COV notifications
With the following objects, the change amount of a PresentValue property which sends COV notifications can be set to a
CovIncrement property.
• AnalogInput object
• AnalogOutput object
• AnalogValue object
1. Select [BACnetObject] to open the "BACnet Objects" screen.
2. Click the [Browse] button of an ObjectType to set a CovIncrement property.
3. Click the [Details] button of an ObjectID to set a CovIncrement property.
4. Click the [Edit] button of "CovIncrement".
5. Set the change amount of a PresentValue property, and click the [Update] button.
■ At the reception of a SubscribeCOV service
A COV notification is sent when a SubscribeCOV service is received from a BACnet device.
The setting is unnecessary because a BACnet module automatically sends COV notifications.