1 FUNCTIONS
1.1 BACnet Object Function
23
1
Buffer memory format of AnalogInput objects
The following shows the format of properties assigned to the buffer memory.
Additionally, the availability of reading from/writing to a CPU module is shown in the following table.
R: Read-only, W: Write-only, R/W: Read/Write
*1 For details on data conversion, refer to the following section.
Page 170 Data conversion
Offset Name Remarks R/W
+0 CONTROL b15 OutOfService 0: False, 1: True
When '1' is set to "OutOfServiceControl" in [Settings] [Basic
Information] [BACnet Detail Setting] button "Interface", the
value of an OutOfService property is stored.
R/W
b14 to b4
b3 to b0 Reliability 0: NoFaultDetected
1: NoSensor
2: OverRange
3: UnderRange
4: OpenLoop
5: ShortedLoop
6: NoOutput
7: UnreliableOther
8: ProcessError
9: MultiStateFault
10: ConfigurationError
+1 STATUS b15 LimitEnable LowLimitEnable 0: False, 1: True R
b14 HighLimitEnable 0: False, 1: True
b13 to b11 EventState 0: Normal
1: Fault
2: Offnormal
3: HighLimit
4: LowLimit
5: LifeSafetyAlarm
b10 AckedTransition ToOffnormal 0: False, 1: True
b9 ToFault 0: False, 1: True
b8 ToNormal 0: False, 1: True
b7 Not used
b6 EventEnable ToOffnormal 0: False, 1: True
b5 ToFault 0: False, 1: True
b4 ToNormal 0: False, 1: True
b3 StatusFlags InAlarm 0: False, 1: True
b2 Fault 0: False, 1: True
b1 Overridden Always 0
b0 OutOfService 0: False, 1: True
+2 to
+3
PresentValue The data type is a 32-bit unsigned real number.
When a data conversion
*1
setting is configured, data is read as 16-
bit signed integer and converted to 32-bit floating point real
number, then the value is stored to a PresentValue. The offset +3
is not used.
R/W