APPX
Appendix 1 I/O Signals
255
A
Restart request from a configuration function
When the [Restart] button is clicked in a configuration function, an operation restart processing is performed with the following
procedure.
CheckYDevice in the BACnet detail setting is '0'
CheckYDevice in the BACnet detail setting is '1'
Operation of a BACnet module X0 X1 X2 Remarks
The BACnet communication is stopped. 1 0 0
The [Restart] button is clicked in a configuration
function.
When the [Restart] button is clicked in a configuration function, the
value of X1 is changed to '1'.
01
BACnet joining processing is started. 1
After the module has joined to BACnet, the value of X2 is changed
to '1'.
01
A BACnet communication is started. 1
Operation of a BACnet
module
X0 X1 X2 Operation in a program Y1 Remarks
The BACnet communication is
stopped.
100 0
The [Restart] button is clicked in a
configuration function.
When the [Restart] button is
clicked in a configuration function,
the value of X1 is changed to '1'.
01 
1 When the value of X1 is changed
to '1', the initial value is written to
the buffer memory.
After the initial value is written, the
value of Y1 is changed to '1'.
01
When the value of Y1 is changed
to '1', BACnet joining processing is
started.
1
After the module has joined to
BACnet, the value of X2 is
changed to '1'.
01 
A BACnet communication is
started.
1 