APPX
Appendix 2 I/O Signals
Operating condition setting completed flag
■Device number
The following shows the device number of this input signal.
When changing values of the buffer memory, use Operating condition setting completed flag (X9) as an interlock condition to
turn on and off 'Operating condition setting request' (Y9). For the buffer memory addresses which require turning on and off of
'Operating condition setting request' (Y9) to enable the changed values, refer to the following.
Page 125 List of buffer memory addresses
When 'Operating condition setting completed flag' (X9) is off, the A/D conversion is not performed.
When 'Operating condition setting request' (Y9) is on, 'Operating condition setting completed flag' (X9) turns off.
Signal name CH1 to CH16
Operating condition setting completed flag X9
OFF
OFF
ON ON
ON
ON
ON
ON
OFF
'Module READY' (X0)
'Operating condition setting
completed flag' (X9)
'Operating condition setting
request' (Y9)
'A/D conversion completed
flag' (XE)
Controlled by the A/D converter module
Controlled by the program