Appendix 2 I/O Signals
Channel change completed flag
When changing a channel to perform the offset/gain setting, use Channel change completed flag (XB) as an interlock
condition to turn on and off 'Channel change request' (YB).
When the offset/gain setting is configured from the offset/gain setting window of an engineering tool, the setting is performed
properly on the window. Therefore, a program is not required to perform the setting.
When a sequence program used for the MELSEC-Q series A/D converter module is utilized to configure the offset/gain
setting, check that this flag is used as an interlock.
For the sequence programs for the MELSEC-Q series A/D converter module, refer to the following.
Channel Isolated Analog-Digital Converter Module/Channel Isolated Analog-Digital Converter Module (With Signal
Conditioning Function) User's Manual
Device number
The following shows the device number of this input signal.
Signal name CH1 to CH16
Channel change completed flag XB
OFF
OFF
ON
ON
OFF
OFF
Offset/gain setting mode
(offset specification),
offset/gain setting mode
(gain specification)
'Channel change completed
flag' (XB)
'Channel change request' (YB)
Controlled by the A/D converter module
Controlled by the program
Offset setting/gain setting channel