Appendix 3 Buffer Memory Areas
CH1 Offset/gain setting mode (range specification)
In the offset/gain setting, specify the current input or voltage input for each channel.
• When a value other than 0 and 1 is set, the setting is regarded as Current (1).
• When an offset/gain value is written in the offset/gain setting mode (When 'User range write request' (YA) is turned off and
on), this setting is written to a flash memory.
• This setting is saved in the module-specific backup parameter at the online module change. After the module replacement,
the factory default setting to be referred to is determined according to this setting when the offset/gain setting is restored.
■Buffer memory address
The following shows the buffer memory address of this area.
•CH Offset/gain setting mode (range specification)
■Default value
The default value is Voltage (0) for all channels.
At the following timings, the value saved in the flash memory is set.
• When 'Operating condition setting request' (Y9) is turned off and on
• When the operation mode is switched to the offset/gain setting mode
Offset/gain setting mode (range specification) [Q compatible mode]
In the offset/gain setting of the Q compatible mode, specify the current input or voltage input for each channel.
■Buffer memory address
The following shows the buffer memory address of this area.
Only the R60AD8-G can use this area.
■Default value
The default value is Voltage (0).
Setting Setting content
0 Voltage
1 Current
CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 CH9 CH10 CH11 CH12 CH13 CH14 CH15 CH16
4164 4165 4166 4167 4168 4169 4170 4171 4172 4173 4174 4175 4176 4177 4178 4179
(1) 0: Voltage, 1: Current
(2) b8 to b15 are fixed to 0.
Buffer memory name CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8
Offset/gain setting mode (range specification)
(in Q compatible mode)
26
CH1CH2CH3CH4CH5CH6CH7CH8CH1CH2CH3CH4CH5CH6CH7CH8
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b0b1b2b3b4
(1)(2)