10 FUNCTIONS
10.8 SIL2 A/D Conversion Function
"Transmission interval monitoring time"
"Transmission interval monitoring time" of the R60AD8-G is the time used for monitoring where the master station detects an
error on safety communications (data transmission from the R60AD8-G to the master station). If the interval of safety
communications from the R60AD8-G exceeds the time set in "Transmission interval monitoring time", the master station
detects it as disconnection.
[Navigation window] [Parameter] [Module Information] [R60AD8-G(S2M)] [Module Parameter] [Basic
setting] [Transmission interval monitoring time]
Set "Transmission interval monitoring time" of the R60AD8-G to the value same as the one set in "Sending Interval Monitoring
Time [ms]" on the "Safety Communication Setting" window. ( Page 254 Safety communication setting)
Program by the SIL2 diagnostic FB library
With a project on the SIL2 Process CPU side, create a safety program and standard program and define the I/O of the SIL2
diagnostic FB library. Refer to the following to create programs.
Page 297 EXAMPLE OF OPERATION
Item Setting range
Transmission interval monitoring time 30 to 3000(ms)