10 FUNCTIONS
10.8 SIL2 A/D Conversion Function
Diagnostic processing time of A/D conversion circuit diagnostics
A/D conversion circuit diagnostics consisting of steps (1) to (5) is executed for the number of times corresponding to the
following combination.
Two patterns of digital values for diagnostics
Two modules of R60AD8-G (Main) and R60AD8-G (Sub)
Odd and even number channels
In addition, if the verification result is abnormal, A/D conversion circuit diagnostics is retried up to six times.
Therefore, when "SIL2 A/D conversion cycle setting" is 1000ms (default value), the maximum and maximum values of the
number of times of A/D conversion circuit diagnostics and the diagnostics processing time are as follows.
Number of retries Number of times of
diagnostics
Diagnostics processing time
At start-up During operation
6 (maximum) 56 56s 112s
0 (minimum) 8 8s 16s