298
12 EXAMPLE OF OPERATION
Module parameters for "R60AD8-G(S2M)"
Configure the following settings. For parameters other than the following, use the default values.
Module parameters for "R60DA8-G"
Configure the following settings. For parameters other than the following, use the default values.
Module parameter Description
Basic settings A/D conversion enable/disable setting CH1 to CH4: A/D conversion enabled
Input range setting CH1: 0 to 10V
CH2: 0 to 10V
CH3: 0 to 20mA
CH4: 4 to 20mA
Application settings SIL2 A/D conversion cycle setting 2300ms
Module parameter Description
Basic settings D/A conversion enable/disable setting CH1 to CH4: D/A conversion enabled
Output range setting CH1: -10 to 10V
CH2: -10 to 10V
CH3: 4 to 20mA (Extension)
CH4: 4 to 20mA (Extension)
Application settings Input value shift amount CH3: 4000
CH4: 4000
Refresh settings Digital value Set W0 to W7 to CH1 to CH8 in ascending order.
Example) CH1: W0, CH2: W1 ... CH7: W6, CH8: W7