EasyManua.ls Logo

Mitsubishi Electric R60AD8-G - 1.8 Shift Function

Mitsubishi Electric R60AD8-G
342 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1 FUNCTIONS
1.7 Input Signal Error Detection Function
49
1
Ex.
The following figure shows the operation when an analog input value falls below 2.4mA and returns within the normal range
under the following condition.
Input signal error detection auto-clear enable/disable setting (Un\G162): Enable (0)
Input range: 4 to 20mA
Input signal error detection extension/input signal error detection setting (Un\G47): Upper limit value/lower limit value same,
Enable (0000H)
Input signal error detection lower limit value: 2.4mA
When Input signal error detection auto-clear enable/disable setting is set to Disable (1)
After the analog input value returns within the set range, turn on and off Error clear request (YF).
The A/D converter module arranges the following status when an input signal error is cleared.
Input signal error detection flag (Un\G49) is cleared.
Input signal error detection signal (XC) turns off.
The ALM LED turns off.
Latest alarm code (Un\G3750) is cleared.
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON ON
OFF
ONON
Input signal error detection
upper limit value
Input signal error detection
lower limit value
(2.4mA)
Analog input value
Time
Error
detected
CH2 Input signal error detection flag
(Un\G49, b1)
CH1 Input signal error detection flag
(Un\G49, b0)
Input signal error detection signal
(XC)
ALM LED
Normal
input value
Error
detected
Controlled by the A/D converter module
FlashingLights out Lights out
Controlled by the program
Detection range
Out of detection range
Included
CH1 analog
input value
CH2 analog
input value
CH1 A/D conversion completed flag
(Un\G10, b0)
CH2 A/D conversion completed flag
(Un\G10, b1)

Table of Contents

Related product manuals