9 - 6                         9 - 6 
MELSEC-Q
9   TROUBLESHOOTING 
 
(2) Error storage 
If any of the settings made in the buffer memory or the setting with the intelligent 
function module is outside the setting range, the error occurrence (X8 to XF) 
turns ON and the error code corresponding to the error definition is stored into 
the buffer memory. 
By checking the "error code" of the buffer memory, you can identify the error 
cause. 
 
X/Y device 
CH 
Error occurrence  Error reset request 
Buffer memory address 
of Error code 
1 X8  Y8  16 
2 X9  Y9  48 
3 XA  YA  80 
4 XB  YB  112 
5 XC  YC  144 
6 XD  YD  176 
7 XE  YE  208 
8 XF  YF  240 
 
(3)  Confirmation of error definitions 
GX Developer or GX Configurator-CT is required to check the error definition. 
For details of how to check the error definition, refer to "Section 9.1.1 Confirming 
the error definitions using system monitor of GX Developer" or "Chapter 6 Utility 
Package (GX Configurator-CT)". (Refer to Section 9.3 for details of the error 
codes.)