9   TROUBLESHOOTING 
 
9.2 Error Details 
(1)  Types of errors 
The following errors are detected by the QD60P8-G. 
 
(a) Overflow error 
This error occurs if the accumulating count value overflows (exceeds 
99999999) when the count type of the accumulating counter is the linear 
counter. 
 
To clear this error, turn ON the error reset request (Y8 to YF). Further, to 
start count operation properly, set "1" in the "counter reset request" of the 
buffer memory. 
 
(b)  Buffer memory setting range outside error 
This error occurs if any setting error is found by a check made on the 
values set to the buffer memory when the operating condition setting 
request flag (Y1) turns ON. It occurs if any setting value in the "comparison 
output setting value" or similar of the buffer memory is outside the range. 
 
To clear this error, set a correct value and turn ON the operating condition 
setting request flag (Y1) again. 
 
(c)  Intelligent function module switch setting error 
This error occurs if any setting error is found by a check made on the 
setting values of the switch settings for intelligent function module set in the 
PLC parameter when power is switched from OFF to ON or the 
programmable controller CPU is reset. 
 
To clear this error, set a correct value on GX Developer, perform write to 
PLC, and then switch power from OFF to ON or reset the programmable 
controller CPU. 
 
(d) Module error 
This error occurs if a fault occurs in the module for some reason. 
 
Change the module if the error occurs again after power is switched from 
OFF to ON or the programmable controller CPU is reset.