3 - 8                         3 - 8 
MELSEC-Q
3   SPECIFICATIONS 
 
3.4 Buffer Memory 
3.4.1 List of buffer memory assignments 
The following table indicates the assignment of the QD60P8-G buffer memory. Refer to 
Section 3.4.2 for details of the buffer memory areas. 
The initial values are set to the buffer memory at power-on or when the programmable 
controller CPU is reset. (When power is switched OFF, the setting values in the buffer 
memory are not retained.) 
The sequence program or programmable controller CPU's auto refresh function, 
reads/writes the buffer memory contents. 
The settings are reflected on the module by turning ON the operating condition setting 
request flag (Y1) after the data have been written to the buffer memory. 
 
Buffer memory address 
CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 
Setting details 
Initial 
value 
Read/Write 
0  32  64  96  128 160 192 224 Sampling pulse number  Read only 
1  33  65  97  129 161 193 225 Comparison output selection 
2  34  66  98  130 162 194 226  (L) 
3  35  67  99  131 163 195 227 
Comparison output setting value 
(H) 
4  36  68  100 132 164 196 228 Movement averaging processing selection 
5  37  69  101 133 165 197 229 Number of movement averaging processing 
6  38  70  102 134 166 198 230 Pre-scale function selection 
7  39  71  103 135 167 199 231 Pre-scale setting value 
Read/Write 
enabled 
8  40  72  104 136 168 200 232  (L) 
9  41  73  105 137 169 201 233 
Accumulating count value 
(H) 
10  42  74  106 138 170 202 234  (L) 
11  43  75  107 139 171 203 235 
Input pulse value 
(H) 
12  44  76  108 140 172 204 236 Overflow detection flag 
Read only 
13  45  77  109 141 173 205 237 Counter reset request 
Read/Write 
enabled 
14  46  78  110 142 174 206 238 Carry over detection flag  Read only 
15  47  79  111 143 175 207 239 Carry over reset request 
Read/Write 
enabled 
16  48  80  112 144 176 208 240 Error code  Read only 
17  49  81  113 145 177 209 241 Alarm output selection 
Read/Write 
enabled 
18  50  82  114 146 178 210 242 Alarm output flag  Read only 
19  51  83  115 147 179 211 243 Alarm output setting value upper/upper limit 
20  52  84  116 148 180 212 244 Alarm output setting value upper/lower limit 
21  53  85  117 149 181 213 245 Alarm output setting value lower/upper limit 
22  54  86  118 150 182 214 246 Alarm output setting value lower/lower limit 
23  55  87  119 151 183 215 247 Count cycle change function selection 
24  56  88  120 152 184 216 248 Count cycle setting value 
0 
Read/Write 
enabled 
25  57  89  121 153 185 217 249 
to to to to to to to to 
31  63  95  127 159 191 223 255 
Reserved (N/A) 
   
 
*1: Initial value set at power-on or when the programmable controller CPU is reset.