9   TROUBLESHOOTING 
 
 
 
 
 
Related buffer memory address 
 
CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 
Setting range  Remedy 
 
                   
Accumulating count value 
8 
9 
40 
41 
72 
73 
104 
105 
136 
137 
168 
169 
200 
201 
232 
233 
 
Counter reset request 
 
13  45  77  109 141 173 205 237 
1: Reset request 
(The value automatically turns to "0" after 
completion of a counter reset.) 
Set "1" in the "counter reset 
request" of the buffer memory to 
reset the accumulating count 
value. (This error is cleared when 
the error reset request (Y8 to YF) 
turns ON but requires the counter 
to be reset to perform count 
operation.) 
Comparison output selection 
1  33  65  97  129 161 193 225 
0: Comparison output function invalid 
1: Comparison output function valid 
Comparison output setting value 
2 
3 
34 
35 
66 
67 
98 
99 
130 
131 
162 
163 
194 
195 
226 
227 
0 to 99999999 
Movement averaging processing selection 
4  36  68  100 132 164 196 228 
0: Sampling processing 
1: Movement averaging processing 
Number of movement averaging processing 
5  37  69  101 133 165 197 229 
2 to 60 
Pre-scale function selection 
6  38  70  102 134 166 198 230 
0: Pre-scale function invalid
2: 
 0.1 
4: 
 0.001 
1: 
 1 
3: 
 0.01 
5: 
 0.0001 
Pre-scale setting value 
7  39  71  103 135 167 199 231 
0 to 32767 
Alarm output selection 
17  49  81  113 145 177 209 241 
0: Alarm output function invalid 
1: Alarm output function valid 
Alarm output setting value upper/upper limit 
19  51  83  115 147 179 211 243 
Alarm output setting value upper/lower limit 
20  52  84  116 148 180 212 244 
Alarm output setting value lower/upper limit 
21  53  85  117 149 181 213 245 
Alarm output setting value lower/lower limit 
22  54  86  118 150 182 214 246 
0 to 32767 and upper/upper limit   
upper/lower limit 
 lower/upper limit   
lower/lower limit 
Count cycle change function selection 
23  55  87  119 151 183 215 247 
0: Count cycle change function selection 
invalid 
1: Count cycle change function selection valid
 
Count cycle setting value 
 
24  56  88  120 152 184 216 248 
0: 1s 
1: 100ms 
2: 200ms 
3: 500ms 
Turn ON the error reset request 
(Y8 to YF) of the corresponding 
channel. After this, set a correct 
value and then turn ON the 
operating condition setting 
request flag (Y1).