EasyManua.ls Logo

Mitsubishi QD60P8-G - Page 64

Mitsubishi QD60P8-G
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 - 16 5 - 16
MELSEC-Q
5 DETAILS AND SETTING OF FUNCTIONS
Outline of alarm output function operation
The following gives the outline of the alarm output function operation.
• Example of alarm output operation
Lower/ lower limit value
Lower/ upper limit value
Upper/ lower limit value
Upper/ upper limit value
ON
ON
OFF
OFF
Alarm output flag
bit0 (Lower limit alarm)
bit8 (Upper limit alarm)
Count cycle
• Assuming that the upper/upper limit = upper/lower limit and lower/upper limit =
lower/lower limit, operation is performed as shown below.
bit8 (Upper limit alarm)
Alarm output flag
bit0 (Lower limit alarm)
Lower/ upper limit value
Lower/ lower limit value
Upper/ upper limit value
Upper/ lower limit value
ON
ON
OFF
OFF
POINT
Since the "sampling pulse number" of the buffer memory is updated at intervals
of the count cycle setting value (refer to Section 5.1.4), the alarm output flag also
turns ON/OFF at the timing of the count cycle setting value.
The settings are reflected on the module by turning ON the operating condition
setting request flag (Y1) after setting the values to the buffer memory.

Table of Contents

Related product manuals