7 Description of Function Codes NICE5000 User Manual
- 130 -
Chapter 7 Description of Function Codes
Group F0: Basic Parameters
Function
Code
Parameter
Name
Setting Range Default Unit Property
F0-00
Control mode
0: Sensorless vector control (SVC)
1: Closed-loop vector control (CLVC)
2: Voltage/Frequency (V/F) control
1 - ★
It is used to set the control mode of the system.
•
0: Sensorless vector control (SVC)
It is applicable to low-speed running during no-load commissioning of the asynchronous
motor, fault judgment at inspection, and synchronous motor running on special
conditions.
•
1: Closed-loop vector control (CLVC)
It is applicable to normal running in distance control.
•
2: Voltage/Frequency (V/F) control
It is applicable to equipment detection.
Function Code Parameter Name Setting Range Default Unit Property
F0-01
Command source
selection
0: Operation panel control
1: Distance control
1 - ★
It is used to set the source of running commands and running speed references.
•
0: Operation panel control
The controller is operated by pressing
and
on the operation panel, and
the running speed is set by F0-02 (Running speed under operation panel control). This
method is applicable only to the test or motor no-load auto-tuning.
•
1: Distance control
This method is used in the NICE series integrated elevator controller. During inspection,
the elevator runs at the speed set in F3-11. During normal running, the controller
automatically calculates the speed and running curve for the elevator based on the
distance between the current oor and the target oor within the rated elevator speed,
implementing direct travel ride.
Function Code Parameter Name Setting Range Default Unit Property
F0-02
Running speed under
operation panel control
0.050 to F0-04
0.050 m/s ☆