7 Description of Function Codes NICE5000 User Manual
- 164 -
Function
Code
Parameter Name Setting Range Default Unit Property
F6-50
Service oors 2 of time-based
oor service 3
0–65535
65535 - ☆
F6-51
Service oors 3 of time-based
oor service 3
0–65535
65535 - ☆
F6-52
Service oors 4 of time-based
oor service 3
0–65535
65535 - ☆
These parameters define the time periods of three groups of time-based services and
corresponding service oors.
•
Service oors 1: oors 1–16
•
Service oors 2: oors 17–32
•
Service oors 3: oors 33–48
•
Service oors 4: oors 49–56
In the time period of time-based service, the elevator responds to the service oors set by
the related time-based service parameters, but ignores the service oors set by F6-05, F6-
06, F6-07, and F6-09.
The setting of time-based service oors is the same as that of service oors in F6-05.
During the time-based oor service period, the settings of F6-05, F6-06 and F5-35 are invalid.
If the time periods of the three time-based services are overlapped, the system implements the
service according to the priority: Service 1 > Service 2 > Service 3.
Group F7: Intelligent Commissioning Parameters
This group of parameters is specialized for elevator commissioning.
All the settings are not saved and restore to the default setting after power-off.
Follow the instructions for normal-speed commissioning:
1. Before the commissioning, ensure that the shaft is unobstructed and the related
parameters have been set properly.
2. Run the elevator to the middle oor of the shaft at the inspection speed so as to prevent
wrong running direction.
3. Perform single-oor command commissioning and then perform multi-oor command
commissioning.
4. After the commissioning is complete, check that the parameters in this group are set
properly.
Function Code Parameter Name Setting Range Default Unit Property
F7-00
Car call oor registered 0 to F6-00
0 - ☆