7 Description of Function Codes NICE5000 User Manual
- 196 -
As shown in the preceding gure, LEDs 5, 4, and 3 indicate whether communication of the
present viewed address is normal or interrupted.
LEDs 1 and 2 indicate the communication states of 16 addresses, where each segment
indicates one address, and segment ON means normal and segment OFF means
interrupted.
The addresses indicated by segments of LEDs 1 and 2 for FU-49 to FU-52 are listed in the
following table.
Function
Code
FU-49 FU-50 FU-51 FU-52
LEDs 1
and 2
12
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
12
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
12
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
Function Code Parameter Name Setting Range Default Unit Property
FU-53 Mod2 communication state 1 0
–
65535 0 - ●
FU-54 Mod2 communication state 2 0
–
65535 0 - ●
FU-55 Mod2 communication state 3 0–65535 0 - ●
FU-56 Mod2 communication state 4 0–65535 0 - ●
These parameter display the Mod2 communication state between the HCB of all oors and
the MCB.
Mod2 is used for opposite door control and disability calls.
Mod2 is dened in the similar way as Mod1.
Group FP: User Parameters
Function Code Parameter Name Setting Range Default Unit Property
FP-00 User password 0–65535 0 - ☆
It is used to set the user password.
If it is set to any non-zero number, the password protection function is enabled. After a
password has been set and taken effect, you must enter the correct password in order to
enter the menu. If the entered password is incorrect, you cannot view or modify parameters.
If FP-00 is set to 00000, the previously set user password is cleared, and the password
protection function is disabled.
Remember the password that you set. If the password is set incorrectly or forgotten, contact
Monarch to replace the control board.