NICE5000 User Manual 7 Description of Function Codes
- 187 -
These parameters are used to record the leveling adjustment values. Each parameter
records the adjustment information of two oors, and therefore, the adjustment information
of 56 oors can be recorded totally.
The method of viewing the record is shown in the following gure.
Figure 7-8 Viewing the leveling adjustment record
5
4 3
2
1
First floor
leveling
Second floor
leveling
...
...
> 30: upward leveling adjustment
= 30: no leveling adjustment
< 30: downward leveling adjustment
Maximum
adjustment
range:
±30mm
As shown in the preceding gure, the left two LEDs and the right two LEDs respectively
show the adjustment bases of oor 1 and oor 2. If the value is larger than 30, it is upward
leveling adjustment; if the value is smaller than 30, it is downward leveling adjustment. The
default value "30" indicates that there is no leveling adjustment. The maximum adjustment
range is ±30 mm.
The leveling adjustment method is as follows:
1. Ensure that shaft auto-tuning is completed successfully, and the elevator runs properly
at normal speed.
2. Set Fr-00 to 1 to enable the car leveling adjustment function. Then, the elevator shields
hall calls, automatically runs to the top oor, and keeps the door open after arrival. If the
elevator is at the top oor, it directly keeps the door open.
3. Go into the car, press the top oor button, and the leveling position is changed 1 mm
upward; press the bottom floor button, and the leveling position is changed 1 mm
downward. The value is displayed in the car.
Positive value: up arrow + value, negative value: down arrow + value, adjustment range:
±30 mm
4. After completing adjustment for the current oor, press the top oor button and bottom
oor button in the car at the same time to save the adjustment result. The car display