ioLogik E1200 Series RESTful API Default Address Mappings
C-2
RESTful API Name Description Access
/api/slot/0/io/do doPulseOnWidth DO - Pulse mode - ON width (unit: 1
ms)
read-write
/api/slot/0/io/do doPulseOffWidth DO - Pulse mode - OFF width (unit: 1
ms)
read-write
/api/slot/0/io/do doPulseStatus DO - Pulse mode - status (0: STOP,
1: START)
read-write
/api/slot/0/io/relay
/api/slot/0/io/relay relayIndex Relay - index read-only
/api/slot/0/io/relay relayMode Relay - mode (0: Relay, 1: Pulse) read-only
/api/slot/0/io/relay relayStatus Relay - Relay mode -
status (0: OFF,
1: ON)
read-write
/api/slot/0/io/relay relayTotalCount Relay - Relay mode - total count read-only
/api/slot/0/io/relay relayCurrentCount Relay - Relay mode - current count read-only
/api/slot/0/io/relay relayCurrentCountReset Relay - Relay mode - rest current
count (1: RESET)
read-write
/api/slot/0/io/relay relayPulseStatus Relay - Pulse mode - status (0:
STOP, 1: START)
read-write
/api/slot/0/io/relay relayPulseCount Relay - Pulse mode - count read-write
/api/slot/0/io/relay relayPulseOnWidth Relay - Pulse mode - ON width (unit:
1.5 s)
read-write
/api/slot/0/io/relay relayPulseOffWidth Relay - Pulse mode -
OFF width (unit:
1.5 s)
read-write
/api/slot/0/io/ai
/api/slot/0/io/ai aiIndex AI - index read-only
/api/slot/0/io/ai aiMode AI - mode (0: 0-10 V, 1: 4-
20mA, 2:
0-20mA, 4: 4-20mA burnout)
read-only
/api/slot/0/io/ai aiValueRaw AI - raw value read-only
/api/slot/0/io/ai aiValueScaled AI - scaled value read-only
/api/slot/0/io/ai aiValueRawMin AI - minimum raw value read-only
/api/slot/0/io/ai aiValueRawMax AI - maximum raw value read-only
/api/slot/0/io/ai aiValueScaledMin AI - minimum scaled value read-only
/api/slot/0/io/ai aiValueScaledMax AI - maximum scaled value read-only
/api/slot/0/io/ai aiResetMinValue AI - reset minimum value (1: RESET)
read-write
/api/slot/0/io/ai aiResetMaxValue AI - reset maximum value (1:
RESET)
read-write
/api/slot/0/io/ai aiStatus AI - status (0: normal, 1: burnout, 2:
over range, 3. under range)
read-only
/api/slot/0/io/ai aiBurnoutValue AI - burnout value read-only
/api/slot/0/io/ao
/api/slot/0/io/ao aoIndex AO - index read-only
/api/slot/0/io/ao aoMode AO - mode (0: 0-10 V, 1: 4-
20mA, 2:
0-20 mA)
read-only
/api/slot/0/io/ao aoValueRaw AO - raw value read-write
/api/slot/0/io/ao aoValueScaled AO - scaled value read-only
/api/slot/0/io/rtd
/api/slot/0/io/rtd rtdIndex RTD - index read-only
/api/slot/0/io/rtd rtdSensorType RTD - sensor type read-only
/api/slot/0/io/rtd rtdValueEngineeringMultip
lied
RTD - engineering multiplied value read-only
/api/slot/0/io/rtd rtdValueEngineeringMultip
liedMin
RTD - engineering multiplied
minimum value
read-only
/api/slot/0/io/rtd rtdValueEngineeringMultip RTD - engineering multiplied read-only

Table of Contents