ioLogik E1200 Series Introduction
1-10
ioLogik E1242
4 channels
4 channels
4 channels
3k VDC or 2k Vrms
Wet Contact (NPN or PNP), Dry Contact
DI or Event Counter
4 points per COM
250 Hz
Software Configurable
Sink
DO or Pulse Output
500 Hz
-Voltage Protection: 45 VDC
-Current Protection: 2.6 A (4 channels @ 650 mA)
-Temperature Shutdown: 175°C (typical), 150°C (min.)
200 mA per channel
Differential input
16 bits
Voltage / Current (jumper selectable)
0 to 10 VDC, 0 to 20 mA, 4 to 20 mA, 4 to 20 mA (burnout detection)
-10 and 60°C
-40 and 75°C
samples/sec
10 mega-ohms (min.)
-in Resistor for Current Input: 120 ohms
12 to 36 VDC
139 mA @ 24 VDC
502,210 hrs
Telcordia SR332

Table of Contents

Other manuals for Moxa Technologies ioLogik E1210

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Moxa Technologies ioLogik E1210 and is the answer not in the manual?

Moxa Technologies ioLogik E1210 Specifications

General IconGeneral
TypeNetwork transmitter & receiver
Maximum transfer distance- m
Mean time between failures (MTBF)671345 h
Operating temperature (T-T)-40 - 167 °F
Cabling technology10/100Base-T(X)
Ethernet LAN (RJ-45) ports2
Input current0.11 A
AC input voltage24 V
Storage temperature (T-T)-40 - 85 °C
Operating relative humidity (H-H)5 - 95 %
CertificationFCC Part 15 Subpart B Class A, IEC 61000-4, IEC 61000-6
Product colorSilver
Weight and Dimensions IconWeight and Dimensions
Depth84 mm
Width27.8 mm
Height124 mm
Weight200 g