ioLogik E1200 Series Using the Web Console
3-25
When Trigger = Smaller, Value = 400, and Hysteresis = 200, the SNMP trap will only be triggered if the TC
signal fluctuates from 600 to 400, like in scenario 1. If we change to Value = 400 and Hysteresis = 400, the
SNMP trap will only be triggered if the TC signal fluctuates from 800 to 400.
Accessibility IP List
You can control network access to the ioLogik E1200 from the Accessibility IP List page by enabling access
only from specific IP addresses. When the Enable the accessibility IP list checkbox is enabled, a host’s IP
address must be provided and enabled in the list in order to gain access to the ioLogik E1200.
Enable access for a range of IP addresses by specifying the IP address and netmask, as follows:
To allow access for a specific IP address
Enter the IP address in the IP Address field and 255.255.255.255 in the Netmask field.