6 Installation
Messko GmbH 2020 37BA4001150/10 EN MSENSE
®
DGA 2/3
WARNING
Electric shock
Risk of fatal injury due to electrical voltage.
► Maintain the necessary distance from the active part of the transformer
(see Device dimensions with 285 mm measuring pipe length [►Section
14.1, Page 93] and Device dimensions with 507 mm measuring pipe
length [►Section 14.2, Page 94]).
Figure23: Pushing the device into the system
15. Tighten the ball valve clamp connection using a wrench (wrench size70)
with a torque of 140Nm.
Figure24: Securing the MSENSE