7 Commissioning
Messko GmbH 2020 53BA4001150/10 EN MSENSE
®
DGA 2/3
7.3 Commissioning in existing systems
Messko GmbH recommends a field calibration of the device parameters to
ensure optimum operation, in particular with:
Aged insulating oils
Modified oils (e.g. the addition of additives)
Oils that do not satisfy the standards ASTMD3486-091, IEC60296 or
IEC60422.
Here, an oil sample must be taken in accordance with the chapter "Taking oil
samples" [Section 10.3, Page 70] and sent to Messko GmbH together
with the "SAMPLE DATA SHEET – OIL ANALYSIS". You will then receive a
recommendation for action from MESSKO for readjustment via the
MESSKO® MSET parameterization software.
7.4 Parameterization
Parameterization of the device is only possible in combination with the
MESSKO® MSET parameterization software, and is described in detail in
the corresponding operating instructions.
The set values for the gas carbon monoxide (CO) are only available for the
device version MSENSE® DGA 3.
The following settings can be configured for the parameters CO, H2
and H2O (as relative or absolute):
Concentration warning limit
Concentration alarm limit
Gas formation rate warning limit
Gas formation rate alarm limit
Value for 4mA signal
Value for 20mA signal
Concentration action warning limit
Concentration action alarm limit
Gas formation rate action warning limit
Gas formation rate action alarm limit
Other settings
H2O reference
Measurement interval
Time stamp
UNIX time stamp
Service code
Action maintenance information
Modbus baud rate