6 Installation
Messko GmbH 202042 BA4001150/10 ENMSENSE
®
DGA 2/3
Ensure that the protective conductor cross-section is at least the same as
all other connection conductors.
6.3.5 Device grounding
Connect the ground connection on the device ball valve to the transformer
ground connection.
Figure29: Ground connection
With offshore devices, the grounding point of the ball valve is to be greased
(see chapter Ensuring offshore capability [Section 6.4, Page 48]).
6.3.6 Analog outputs
The device has passive, electrically isolated 4...20 mA analog outputs for
the remote transmission of the measured values.
The output signals can be configured using the MESSKO®MSET parame-
terization software.