14 Appendix
Messko GmbH 202098 BA4001150/10 ENMSENSE
®
DGA 2/3
14.5 Data point table for Modbus RTU
Separate input register
No. Address Size Description Designation
1 0 1 byte On / Off CO limit 1
2 1 1 byte On / Off CO limit 2
3 2 1 byte On / Off H2 limit 1
4 3 1 byte On / Off H2 limit 2
5 4 1 byte On / Off H2O limit 1
6 5 1 byte On / Off H2O limit 2
7 6 1 byte On / Off CO rate limit 1
8 7 1 byte On / Off CO rate limit 2
9 8 1 byte On / Off H2 rate limit 1
10 9 1 byte On / Off H2 rate limit 2
11 10 1 byte On / Off H2O rate limit 1
12 11 1 byte On / Off H2O rate limit 2
13 12 1 byte On / Off Maintenance in 6 months
14 13 1 byte On / Off Maintenance required
15 14 1 byte On / Off CO Value Valid
1)
16 15 1 byte On / Off H2 Value Valid
1)
17 16 1 byte On / Off H2O Value Valid
1)
18 17 1 byte On / Off H2O mode %RH
1)
If the "Value Valid = Off" status is present, it means the same as an aster-
isk (*) in the display or in the MSET status display, and the system is outside
the specified measuring range in accordance with the "Technical
data" [►Section 13, Page 90] chapter. The following applies to the transmit-
ted measured value:
▪ During the first measurement after the running-in phase, the value of the
lower detection limit is transmitted.
▪ If measured values within the specified measuring range have already
been recorded, then the last valid measured value is transmitted.
If the status changes to "Value Valid = On", then the system is back in the
valid measuring range.
Input register
No. Address
(dec.)
Size Description Designation
1 0 4 bytes,
SFLOAT
None CO value ppm
2 2 4 bytes,
SFLOAT
None H2 value ppm
3 4 4 bytes,
SFLOAT
None H2O value ppm
4 6 4 bytes,
SFLOAT
None Oil temperature