EasyManua.ls Logo

MR MSENSE DGA 2 - Data Point Table for Modbus RTU

MR MSENSE DGA 2
104 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14 Appendix
Messko GmbH 202098 BA4001150/10 ENMSENSE
®
DGA 2/3
14.5 Data point table for Modbus RTU
Separate input register
No. Address Size Description Designation
1 0 1 byte On / Off CO limit 1
2 1 1 byte On / Off CO limit 2
3 2 1 byte On / Off H2 limit 1
4 3 1 byte On / Off H2 limit 2
5 4 1 byte On / Off H2O limit 1
6 5 1 byte On / Off H2O limit 2
7 6 1 byte On / Off CO rate limit 1
8 7 1 byte On / Off CO rate limit 2
9 8 1 byte On / Off H2 rate limit 1
10 9 1 byte On / Off H2 rate limit 2
11 10 1 byte On / Off H2O rate limit 1
12 11 1 byte On / Off H2O rate limit 2
13 12 1 byte On / Off Maintenance in 6 months
14 13 1 byte On / Off Maintenance required
15 14 1 byte On / Off CO Value Valid
1)
16 15 1 byte On / Off H2 Value Valid
1)
17 16 1 byte On / Off H2O Value Valid
1)
18 17 1 byte On / Off H2O mode %RH
1)
If the "Value Valid = Off" status is present, it means the same as an aster-
isk (*) in the display or in the MSET status display, and the system is outside
the specified measuring range in accordance with the "Technical
data" [Section 13, Page 90] chapter. The following applies to the transmit-
ted measured value:
During the first measurement after the running-in phase, the value of the
lower detection limit is transmitted.
If measured values within the specified measuring range have already
been recorded, then the last valid measured value is transmitted.
If the status changes to "Value Valid = On", then the system is back in the
valid measuring range.
Input register
No. Address
(dec.)
Size Description Designation
1 0 4 bytes,
SFLOAT
None CO value ppm
2 2 4 bytes,
SFLOAT
None H2 value ppm
3 4 4 bytes,
SFLOAT
None H2O value ppm
4 6 4 bytes,
SFLOAT
None Oil temperature

Table of Contents

Related product manuals