Presignal and Positive Alarm Sequence (PAS)
$
SS
HQGL[%6
S
HFLDO =RQH 2XW
S
XWV
AFC-600 Programming PN 51032:A 3/8/99 69
$
SS
HQGL[%6
S
HFLDO=RQH2XW
S
XWV
3UHVLJQDODQG3RVLWLYH$ODUP6HTXHQFH3$6
:KDWLV3UHVL
J
QDODQG3$6"
3XU
S
RVH
Presignal is a feature that initially causes alarm signals to only sound in specific areas,
monitored by qualified persons, where activating a general alarm requires human
verification. This allows delay of the alarm up to 180 seconds after the start of alarm
processing. The control panel Presignal feature provides two selections:
1RWH
3UHVL
J
QDO GLIIHUV IURP WKH
$ODUP 9HULILFDWLRQ 7LPHU ZKLFK
GRHV QRW UH
T
XLUH KXPDQ
LQWHUYHQWLRQ
A
Presignal Delay Timer
(60-180 seconds) that delays activation of all outputs
with a CBE that includes Special Zone F0.
A
PAS
(Positive Alarm Sequence) selection, in addition to the
Presignal Delay
Timer
, that allows a 15-second time period for acknowledging an alarm signal
from a fire detection/initiating device. If the alarm is not acknowledged within 15
seconds, all local and remote outputs activate immediately and automatically.
Figure 78 contains an illustration of Presignal and PAS timing.
)LJXUH  3UHVLJQDO DQG 3$6 7LPH
The control panel delays activation of outputs containing F0 in their Control-By-Event
(CBE) list for all alarm initiating devices that contain F0 in their CBE list. A subsequent
alarm will abort the Presignal Delay Timer and execute CBE lists.
1RWHV RQ XVLQ
J
)
NFPA 72 requires installation of a PAS Inhibit switch, that you can use to turn off
the PAS delay timer when the control panel is unattended. Do so by programming a
monitor module with the Type Code,
PAS
INHIBIT
. For details, refer to "How to
Program a Monitor Module" on page 23.
Abort circuit activation by pressing the
ALARM
SILENCE
key before the Presignal
Delay Timer expires.
Program zone F0 to participating inputs and outputs.
5HVWULFWLRQV RQ XVLQ
J
)
Do not include F0 in the CBE list for a releasing device.
Do not include F0 in the CBE list for any monitor module that connects to a device
other than an automatic fire detector.
Continued on the next page...
3UHVL
J
QDO 'HOD
\
7LPHU  V
3$6 V
,QLWLDO DODUP
DQQXQFLDWLRQ
$ODUP DFWLYDWHV RXW
S
XWV LI WKH
FRQWURO
S
DQHO LV QRW UHVHW
,I 3$6 < DODUP DFWLYDWHV
RXW
S
XWV LI QRW DFNQRZOHG
J
HG
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Notifier AFC-600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFC-600 and is the answer not in the manual?

Notifier AFC-600 Specifications

General IconGeneral
BrandNotifier
ModelAFC-600
CategoryFire Alarms
LanguageEnglish

Related product manuals