Presignal and Positive Alarm Sequence (PAS)
70 AFC-600 Programming PN 51032:A 3/8/99
6HOHFWLQ
3UHVL
QDODQG3$62XW
XWV
3UHVL
QDO
You can set Presignal Delay Timer between 60 and 180 seconds. A Presignal Delay
Timer does not apply to the following:
• The System Alarm relay (TB3 on the MPS-6)
• The 4XTM polarity reversal alarm output
• The 4XTM municipal box output
3RVLWLYH $ODUP 6H
XHQFH
3$6
Outputs selected for PAS delay for 15 seconds. Pressing the
ACKNOWLEDGE
/
STEP
key
within the 15-second delay increases the Presignal Delay Timer to the full programmed
value (60-180 seconds). When an alarm comes from an initiating device with a CBE list
that includes F0, the control panel delays the following outputs:
• System Alarm relay (TB3 on the MPS-6)
• 4XTM Polarity Reversal Alarm output
• 4XTM Municipal Box output