How to Use the Basic Program
32 AFC-600 Programming PN 51032:A 3/8/99
+RZWR&KDQ
J
H*OREDO6
\
VWHP)XQFWLRQV
6<67(0
The System option lets you select settings for global system functions that apply to all
programmed devices and zones. For instance, selecting an Alarm Verification Timer for
30 seconds means that all initiating devices selected for Alarm Verification use a
30-second timer. From the Program Change screen (Figure 8 on page 15), press the
7
key to display the System Function screen:
)LJXUH  6\VWHP )XQFWLRQ 6FUHHQ
*OREDO 6
\
VWHP )XQFWLRQV
Table 18 contains settings for global system functions.
7DEOH  6HWWLQ
J
V IRU *OREDO 6
\
VWHP )XQFWLRQV
&
3UR
J
UDP &KDQ
J
H
S
DVVZRUG
&
)
WR H[LW
6,/ ,1+  $872  9(5,)<  86$ 7,0(
7(50 1 $&
B
'/< < /RF7 %/,1.  67 $&6 1
System Function Setting Default
SIL INH (Silence Inhibit Timer) 0 to 300 seconds 000
AUTO (Auto Silence Timer) 000 (none)
600 to 900 seconds
000
VERIFY (Alarm Verification Timer) 0 to 30 seconds 30
USA TIME
USA time (mm/dd/yy) or
EUR time (dd/mm/yy)
Press the
NEXT
or
PREVIOUS
key to
change. Note that (European) time
changes to 24-hour time format
and date format
USA TIME
TERM Allows supervision for devices
connected to TB3, i.e. LCD-80.
N no supervision
Y supervision enabled
N0
AC_DLY=Y AC delay delays loss of AC
reporting for 8 hours.
Y=AC delay
N=no AC delay
Y
LocT Terminal mode one of three
operating modes of PC or terminal
connected to the control panel through
TB2 on the CPU.
Note: For a complete list of functions,
refer to the AFC-600 Installation Manual.
LocT (terminal connected
to control panel and
located in same room)
LocM (same as LocT but
requires password)
RemT (terminal connected
through a modem for Read
Status only)
LocT
BLINK=01 (addressable SLC device
LED blink)
Blink - Select from 00 to 16.
(00 = no blink, 01 = blink every
poll, 02 = blink every 2nd poll, 03
= blink every 3rd poll up to 16 =
blink every 16th poll) - Note: this
setting effects FlashScan devices
only.
01
ST=4 the NFPA wiring style used for
the SLC.
ST=6 (Style 6 SLC wiring)
ST=4 (Style 4 SLC wiring)
ST=4
ACS Use ACS Selection Groups (Refer
to Annunciator Options on page 33).
N or Y ACS=N