AWACS Overview
$
SS
HQGL[ & $:$&6 $
SS
OLFDWLRQV
AFC-600 Programming PN 51032:A 3/8/99 73
$
SS
HQGL[&$:$&6$
SS
OLFDWLRQV
$:$&62YHUYLHZ
AWACS (Advanced Warning Addressable Combustion Sensing) is a set of software
algorithms that provide the AFC-600 with industry-leading smoke detection capability.
You can program AWACS functions on a global or on a per-detector basis as listed in
Table 37, which lists the AWACS topics covered in this appendix:
7DEOH $:$&6 7R
S
LFV
$:$&6)HDWXUHV
AWACS features include the following:
Drift Compensation and Smoothing
Maintenance Warnings
Sensitivity Adjust
Self-optimizing Pre-Alarm
Cooperative Multi-Detector Sensing
Pre-Alarm
'ULIW&RP
S
HQVDWLRQ
Drift compensation uses algorithms (U.S. patent pending) that identify and compensate
for long-term changes in the analog readings from each smoke detector. (Typically,
dirt and dust accumulation inside the smoke chamber causes long-term changes in
detector readings.) Drift compensation does the following:
Allows a detector to retain its original ability to detect actual smoke, and resist
false alarms, even as dirt and dust accumulates.
Reduces maintenance requirements by allowing the control panel to automatically
perform the periodic sensitivity measurements required by NFPA Standard 72.
AFC-600 software also provides smoothing filters to remove transient noise signals,
usually caused by electrical interference. Different smoothing algorithms are used,
depending on the sensitivity selection of each detector. Refer to Detector Sensitivity
Settings on page 79 for more information on detector sensitivity levels.
Continued on the next page...
Top i c Refer to Pag e
AWACS features Descriptions of AWACS features, such as Drift
Compensation, Sensitivity Adjust, programmable on a per-detector
basis.
73
Pre-Alarm Alert and Action settings, programming (global settings). 78
Detector Sensitivity Settings Pre-Alarm and Alarm sensitivity settings
for photo, ion, laser, and multisensor detectors programmable on a per-
detector basis.
79
Detector Maintenance Features Instructions for viewing and printing
detector maintenance information.
81
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Notifier AFC-600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFC-600 and is the answer not in the manual?

Notifier AFC-600 Specifications

General IconGeneral
BrandNotifier
ModelAFC-600
CategoryFire Alarms
LanguageEnglish

Related product manuals