Detector Sensitivity Settings
80 AFC-600 Programming PN 51032:A 3/8/99
+RZWR7HVW'HWHFWRUV6HW%HORZ2EVFXUDWLRQ
S
HU)RRW
Using alarm sensitivities below 0.50% obscuration per foot requires a 90-day test to
ensure that the detector environment is suitable for the higher sensitivity setting. To
meet Notifier and Underwriters Laboratory requirements, test each detector planned to
operate below 0.50%/ft obscuration as follows:
1. Set the detector as follows:
2. Operate detectors continuously for 90 days with all environmental factors (such as,
temperature, humidity, air flow, occupancy, and so on) similar to the intended
application for the detectors. Record all events for each tested detector with an
electronic History buffer or a printout.
3. At the end of the 90-day test: An authorized Notifier representative, or an end user
trained by an authorized Notifier representative must inspect the results of the test.
If the test results show no alarms or pre-alarms for the tested detectors, reprogram
the fire alarm system to set the Alarm sensitivity to the more sensitive Pre-Alarm
level.
Step Action
1 Initially set to the 0.50% obscuration per foot Alarm level.
2 Set the Pre-Alarm level to the desired final Alarm sensitivity.
3 Set the Pre-Alarm to Alert mode (non-latching).
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Notifier AFC-600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFC-600 and is the answer not in the manual?

Notifier AFC-600 Specifications

General IconGeneral
BrandNotifier
ModelAFC-600
CategoryFire Alarms
LanguageEnglish

Related product manuals