Field-Wiring the Modules
,QVWDOODWLRQ
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 2-27
)L H OG :LULQJD Q ,&0 DQ G DQ,&(1 )3$6W\OH< D QG =
Guidelines for field-wiring include the following:
• Notification Appliance Circuits (NACs) are supervised, power-limited, and can
connect to an energy-limited cable.
• Use only the compatible, UL-listed notification appliances listed in the Device
Compatibility Document.
• Wire notification appliances according to the manufacturer's instructions.
• Maximum current per circuit is 3.0 A. Maximum current per module depends on
the type of power supply (MPS-400 or AVPS-24).
• Canadian installations require model N-ELR End-of-Line Resistor Assembly
(Style Y only).
• Size NAC wiring so the voltage drop does not exceed the minimum rated voltage of
the notification appliance used as the last device on the circuit.
• For zone coded applications, refer to the UZC-256 manual.
• The ICM-4 is California Code programmable (microprocessor Rev. B or higher).
To program for California Code, cut diode D35.
)LJXUH )LHOG:LULQJ DQ ,&0
Positions E, F, G, and H are active only with the ICE-4 installed. You can also install a
CRE-4 module on the ICM-4, connected as shown in Figure 2-36:
)LJXUH )LHOG:LULQJ DQ ,&(
% $ $¤ %¤ % $ $¤ %¤ % $ $¤ %¤ % $ $¤ %¤