IFS-2600 Fire Indicator Panel Section 3 Operation
DOC-01-009 9
For IFS-2005 & IFS-2006 Boards:
This function tests the performance of the batteries fitted to the system. Pressing this button will initiate a
battery test as specified in AS4428. The test will temporarily disconnect the batteries from the panel and
apply load on the batteries for 15 seconds.
The result of the test will be displayed on the LED's. If the "Battery Fault" LED is on, only a successful
battery test will turn the LED off. The pressing of any key during the test period will abort the battery test
and return the system back to normal mode.
This function will perform a fixed automatic test procedure to the panel. This mode cannot be selected if
any zone(s) is in alarm. Auto test will perform the following test functions;
1. Displays firmware revision REV-6
2. Turn on ALL LEDs for 0.5 seconds
3. Test LCD Backlighting
4. Test Panel memory(E
2
ROM & RAM)
5. Test LCD
6. Isolate all alarm zones
7. Fault test all alarm zones
8. Alarm test all alarm zones
9. Test buzzer (Beeps twice)
WALK TEST MODE
WALK
TEST
This function will place the panel into "walk test" mode. Walk test mode is used for the on-site testing of
detector zones. This mode cannot be selected if any zone(s) are in alarm.
When WALK TEST button is pressed, panel will be automatically placed in walk test mode, which is
acknowledged by two buzzer beeps and LCD displays WALK TEST MODE, PRESS ANY KEY TO
EXIT”.
Selecting any key from the keypad triggers the buzzer to beep twice and activates the BELL relay leading
BELL ACT LED to blink thrice.
NOTE:
Battery test function is disabled when the panel is in alarm condition.
AUTO TEST MODE
AUTO
TEST
NOTE:
Pressing of any key during "AUTO TEST" will abort the tests and return the system back
to normal mode once the current test is complete.
During "AUTO TEST", all zones are treated as zone type #1 (standard latching type with
2 Second delay). Once AUTO TEST has finished, all zones will be reset and returned
back to their previously configured types.

Other manuals for Notifier IFS-2600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier IFS-2600 and is the answer not in the manual?

Notifier IFS-2600 Specifications

General IconGeneral
BrandNotifier
ModelIFS-2600
CategoryFire Alarms
LanguageEnglish

Related product manuals