IFS-2600 Fire Indicator Panel Section 4 Installation
DOC-01-009 17
Panelect Thermal Type D PFS-D
Panelect Smoke Ionisation PFS-I
Panelect Smoke Ionisation PFS-I , MkII
Panelect Smoke Photo Optical PFS-P
Panelect Smoke Photo Optical PFS-P, MkII
Table 4-1, Compatible Detectors
4.2. Specification
General
Approvals:
Australian Standard AS4428.1 1998
Approval No AFP-1553
C-Tick Approval No. N1336
Environmental Limits:
-10 Deg.C to +55 Deg.C Dry heat.
+40 Deg.C @ 93% Relative Humidity.
Specification for IFS-2600 in CAB650/CAB900:
Cabinet Zinc Sealed Steel 1.2mm, Powder Coated, Hinged Inner & Outer
Door
Outside Dimensions Refer to Figure 4-1 & Figure 4-2 for dimensions
Fuses
(NI-2025-01 & NI-2017-01
Boards)
Warning System Fuse F2
M205 1A
Bell Fuse F4
M205 1A
ACF Fuse F6
M205 1A
AUX Fuse F8
M205 1A Slow Blow
Door Holder Fuse F10 M205 3A
AZF Circuits Current Limited 40mA
E.O.L Resistor on AZFs,
monitored outputs, Bells,
Warning system, ACF
4K7 Ohms