EasyManuals Logo

Notifier IFS-2600 User Manual

Notifier IFS-2600
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #52 background imageLoading...
Page #52 background image
IFS-2600 Fire Indicator Panel Section 5
Programming
DOC-01-009 47
Alarm Verification Facility (AVF)
Alarm verification (AVF) is a facility used to minimise false alarms.
AVF only applies to the zones programmed for the AVF function.
Global Programmable Options:
A
larm Verification
1
DISABLED
2
2 MINUTES
3
3 MINUTES
4
4 MINUTES
5
5 MINUTES
Operation is as follows:
If a zone is programmed as AVF and it registers an alarm, no alarm functions are performed, if it is the first
AVF zone in alarm.
This zone and all other zones programmed as AVF zones are reset by shutting down power to their
detectors for 12 seconds, the power is then restored and the zones are re- enabled.
The alarm verification zones are now in "alert" mode. Any AVF zone going into alarm within the pre-
selected timeout period (2,3,4,5 minutes) will then cause an immediate alarm condition with all the
programmed output functions being initiated.
If no alarm is received within this period, the AVF zones are removed from the "alert" mode and returned to
normal. A further alarm will re-initiate the reset sequence etc.
Other zones are unaffected by the actions of AVF zones. They will all function as normal, regardless of
AVF zone status.
If the timeout period is disabled, the alarm will transmit instantly thus making the AVF non-functional.
AVF TIMEOUT
(3 MINUTES)
Use the "NEXT" & "PREVIOUS" keys to scroll through:
DISABLED
2 MINUTES
3 MINUTES
4 MINUTES
5 MINUTES
RELAY (Global Relay Unity MAP)
MAP RELAY (XX) >>
FROM ZONE (XX)
NOTE:
The option previously set is displayed in brackets and is the first to be displayed.

Other manuals for Notifier IFS-2600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier IFS-2600 and is the answer not in the manual?

Notifier IFS-2600 Specifications

General IconGeneral
BrandNotifier
ModelIFS-2600
CategoryFire Alarms
LanguageEnglish

Related product manuals