IFS-2600 Fire Indicator Panel Section 3 Operation
DOC-01-009 13
If a correct entry is made, the zone is immediately isolated. If the zone is already in alarm, all of its alarm
outputs are isolated and indicators remain visible.
If the "ALL" function is performed, all zones will be isolated, regardless of their previous state. Performing
the "ALL" function for a second time will de-isolate all zones.
RESET
RESET # ENTER
The reset function momentarily disconnects power, and resets all alarm parameters for the zone(s) being
reset. This returns the zone back to its "normal" state.
‘#’ in the above key sequence is the zone number.
If only one zone is to be reset, type in the zone number. Alternatively the "ALL" button can be used to
simultaneously reset all zones.
To perform a reset on a particular zone or on all zones:
1. Press the "RESET" button. The buzzer will give 2 short beeps to indicate that reset mode has
been entered.
2. The LCD display will read "ALARM RESET MODE, ENTER ZONE NO".
3. Enter the zone number ("#") 1-64 or “all”.
4. Press "ENTER".
A long beep will signify an incorrect entry and will revert back to normal operating mode. The "RESET"
button will need to be pressed again to re-enter reset mode.
If a correct entry is made, resetting of the zone begins immediately. Any alarm indication will be removed
immediately; also resetting the zone(s) programmed outputs.
NOTE:
If the Zone is still active after the RESET function, it will automatically revert back to
alarm mode.