Command Formats cont.
DATAFORMAT is used for V01 command or Continuous Mode (RS-232).
DATAFORMAT.0 = 0 No Status DATAFORMAT.1 = 0 No Reading DATAFORMAT.2 = 0 No Peak
1 Alarm Status 1 Reading 1 Peak
DATAFORMAT.3 = 0 No Valley DATAFORMAT.6 = 0 No Unit DATAFORMAT.7 = N/A
1 Valley 1 Unit
Example: Set Space, Continuous, RS-232, Echo, Line Feed, N/A. The command data is 00000110Bin = 06Hex. Send *W1F06.
ADDRESS is applicable for RS-485 and can be 01 to 199.
TRANSMIT TIME INTERVAL is applicable in the RS-232 Continuous Mode which specifies the time between transmissions
and the minimum time is 1 second.