CP TD1 User Manual
28 OMICRON
8. Connect the Control Device to the mains power supply using the provided cable..
9. Turn on the Control Device at its mains power switch.
10.The green warning light lights up, showing that the Control Device’s output does not carry a
dangerous voltage or current yet (on the TESTRANO 600 the blue ring of the Start/Stop button is
additionally lit).
11.An error message appears either if the PE connection is defective or if the power supply has no
galvanic connection to ground. The latter is the case on very special power supplies like with
generators or when insulation transformers are used.
DANGER
Death or severe injury caused by high voltage or current
The high-voltage cable is double-shielded and therefore safe. However, the last 50 cm
(20 inch) of this cable have no shield.
► During a test, consider this cable a life wire and, due to the high-voltage, life-
hazardous.
WARNING
Death or severe injury caused by high voltage or current possible
► Establish a barrier to the high-voltage area.
WARNING
Death or severe injury caused by high voltage or current possible
► If none or both warning lights are on, the unit is defective and must not be used
anymore.
WARNING
Death or severe injury caused by high voltage or current possible
This is a safety-relevant message. If the reason for this message is that neither PE nor
grounding terminal is connected, it can cause injury or possibly death of the operating
staff. The operator is fully responsible for any hazard that might occur due to improper
grounding.
► For safe operation always make sure that both PE and grounding terminal are
connected.