4-33
4-2 Function Mode
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
4
Parameter List
Others
C101
UP/DWN
Storage
Selection
00: Do not store frequency
data
01: Store frequency data
00 no yes 5-71
C102 Reset Selection
00: Trip reset at power-on
01: Trip reset at power-off
02: Enabled only during trip
(Reset when the power is
ON.)
03: Trip reset only
00 yes yes
5-100
C103
Reset Restart
Selection
00: 0 Hz restart
01: Frequency matching
restart
02: Frequency pull-in restart
00 no yes
C104
UP/DWN Clear
Terminal Mode
00: 0 Hz
01: EEPROM data at power-
on
00 no yes 5-71
C105 MP Gain Setting 50. to 200. 100. yes yes % 5-43
C106
AM Gain
Adjustment
50. to 200. 100. yes yes % 5-45
C109 AM Bias Setting 0. to 100. 0. yes yes % 5-45
C111
Overload 1
Warning Level 2
0.00 to 2.00 × Rated current
Rated
current
×
1.15
yes yes A 5-115
Parameter
No.
Function name Monitor or data range
Default
setting
Set data
Data can
be set
during
RUN
Data can be
changed
during RUN
Unit
Page