4-32
4-2 Function Mode
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
4
Parameter List
Communication function
C076
Operation
Selection on
Communication
Error
00: Trip
01: Trip after deceleration
stop
02: Ignored
03: Free-run stop
04: Deceleration stop
02 no yes −
6-3
C077
Communication
Error Timeout
Time
0.00: Timeout disabled
0.01 to 99.99
0.00 no yes s
C078
Communication
Wait Time
0. to 1000. 0. no yes ms
Adjustment
C081 FV Adjustment 0.0 to 200.0 100. yes yes %
5-40
C082 FI Adjustment 0.0 to 200.0 100. yes yes %
C085
Thermistor
Adjustment
0.0 to 200.0 100.0 yes yes % 5-120
C091
Debug Mode
Selection
Use "00". *Do not change. 00 yes yes −−
Communication function
C096
Communication
Selection
00: Modbus communication
(Modbus-RTU)
01: Co-inverter
communication
02: Co-inverter
communication
(management inverter)
00 no no −
6-22
C098
Co-inverter
Communication
Starting Station
Number
1. to 8. 1. no no −
C099
Co-inverter
Communication
Ending Station
Number
1. to 8. 1. no no −
C100
Co-inverter
Communication
Start Selection
00: 485 terminal
01: Always started
00 no no −
Parameter
No.
Function name Monitor or data range
Default
setting
Set data
Data can
be set
during
RUN
Data can be
changed
during RUN
Unit
Page