4-37
4-2 Function Mode
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
4
Parameter List
Control parameter
H030
Motor 1
Parameter R1
(Auto-tuning
Data)
0.001 to 9.999
10.00 to 65.53
Depends
on the
capacity
no no
5-145
H230
Motor 2
Parameter R1
(Auto-tuning
Data)
0.001 to 9.999
10.00 to 65.53
Depends
on the
capacity
no no
H031
Motor 1
Parameter R2
(Auto-tuning
Data)
0.001 to 9.999
10.00 to 65.53
Depends
on the
capacity
no no
H231
Motor 2
Parameter R2
(Auto-tuning
Data)
Depends
on the
capacity
no no
H032
Motor 1
Parameter L
(Auto-tuning
Data)
0.01 to 99.99
100.0 to 655.3
Depends
on the
capacity
no no
mH
H232
Motor 2
Parameter L
(Auto-tuning
Data)
Depends
on the
capacity
no no
H033
Motor 1
Parameter Io
(Auto-tuning
Data)
0.01 to 99.99
100.0 to 655.3
Depends
on the
capacity
no no
A
H233
Motor 2
Parameter Io
(Auto-tuning
Data)
Depends
on the
capacity
no no
H034
Motor 1
Parameter J
(Auto-tuning
Data)
0.001 to 9.999
10.00 to 99.99
100.0 to 999.9
1000. to 9999.
Depends
on the
capacity
no no
kgm
2
H234
Motor 2
Parameter J
(Auto-tuning
Data)
Depends
on the
capacity
no no
H050
V/f Control with
Speed
Feedback Slip
Compensation
Proportional
Gain
0.00 to 10.0 0.20 yes yes
Time
5-83
5-160
H051
V/f Control with
Speed
Feedback Slip
Compensation
Integral Gain
0.0. to 100.0 2 yes yes s
Parameter
No.
Function name Monitor or data range
Default
setting
Set data
Data can
be set
during
RUN
Data can be
changed
during RUN
Unit
Page

Table of Contents

Other manuals for Omron 3G3MX2