6-48
6-8 List of Modbus Communication (Modbus-RTU) Data
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
6
Communication Function
131Dh
Frequency Pull-in
Restart Level
b028 R/W 200 to 2000 0.01 [%]
5-97
5-100
5-103
131Eh
Frequency Pull-in
Restart Parameter
b029 R/W 1 to 30000 0.1 [s]
131Fh
Starting Frequency at
Frequency Pull-in
Restart Selection
b030 R/W
00: Frequency at
interruption
01: Max. frequency
02: Set frequency
−
1320h Soft Lock Selection b031 R/W
00: Data other than b031
cannot be changed
when terminal SFT is
ON
01: Data other than b031
and set frequency
cannot be changed
when terminal SFT is
ON
02: Data other than b031
cannot be changed.
03: Data other than b031
and the set frequency
cannot be changed
10: Data can be changed
during RUN.
− 5-84
1321h Reserved −−− − −
1322h
Motor Cable Length
Code Selection
b033 R/W 5 to 20 − 5-145
1323h
RUN Time/Power ON
Time Level
b034
(HIGH)
R/W
0 to 65535 10 [h] 5-124
1324h
b034
(LOW)
R/W
1325h
Rotation Direction Limit
Selection
b035 R/W
00: No direction limit
01: Only Forward is enabled
(Reverse is limited)
02: Only Reverse is enabled
(Forward is limited)
− 5-23
1326h
Reduced Voltage Startup
Selection
b036 R/W
0 (Reduced voltage startup
time: small) to 255
(Reduced voltage startup
time: large)
− 5-58
1327h Display Selection b037 R/W
00: Complete display
01: Individual display of
functions
02: User setting, + b037
03: Data comparison
display
04: Basic display
05: Monitor display only
− 5-88
1328h Initial Screen Selection b038 R/W
00: Screen on which the
Enter key was last
pressed
001 to 060:
(d001 to d060)
201: F001
202: Do not use this setting.
− 5-86
Register
No.
Function name
Parameter
No.
R/W
Monitor and setting
parameters
Data
resolution
Page