EasyManua.ls Logo

Omron 3G3MX2 - Page 363

Omron 3G3MX2
440 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-60
6-8 List of Modbus Communication (Modbus-RTU) Data
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
6
Communication Function
144Bh
Communication Speed
Selection
C071 R/W
03 (2,400 bps)
04 (4,800 bps)
05 (9,600 bps)
06 (19.2 kbps)
07 (38.4 kbps)
08 (57.6 kbps)
09 (76.8 kbps)
10 (115.2 kbps)
144Ch
Communication Station
No. Selection
C072 R/W 1 to 247
144Dh
Reserved −−
144Eh
Communication Parity
Selection
C074 R/W
00: Disabled
01: Even
02: Odd
144Fh
Communication Stop Bit
Selection
C075 R/W
1: 1 bit
2: 2 bits
1450h
Operation Selection on
Communication Error
C076 R/W
00: Trip
01: Trip after deceleration
stop
02: Ignore
03: Free-run stop
04: Deceleration stop
1451h
Communication Error
Timeout Time
C077 R/W
0: Timeout disabled
0.01 [s]
1 to 9999
1452h
Communication Wait
Time
C078 R/W 0 to 1000 1 [ms]
1453h
to
1454h
Reserved −−
1455h FV Adjustment C081 R/W 0 to 2000 0.1 [%]
5-40
1456h FI Adjustment C082 R/W 0 to 2000 0.1 [%]
1457h
to
1458h
Reserved −−
1459h Thermistor Adjustment C085 R/W 0 to 2000 0.1 [%] 5-120
145Ah
to
145Eh
Reserved −−
145Fh Debug Mode Selection C091 R
For factory adjustment (Do
not change.)
−−
1460h
to
1463h
Reserved −−
1464h
Communication
Selection
C096 R/W
00: Modbus communication
(Modbus-RTU)
01: Co-inverter
communication
02: Co-inverter
communication
(management)
6-22
1465h Reserved −−
Register
No.
Function name
Parameter
No.
R/W
Monitor and setting
parameters
Data
resolution
Page

Table of Contents

Other manuals for Omron 3G3MX2

Related product manuals