6-61
6-8 List of Modbus Communication (Modbus-RTU) Data
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
6
Communication Function
1466h
Co-inverter
Communication Starting
Station Number
C098 R/W 1 to 8
6-221467h
Co-inverter
Communication Ending
Station Number
C099 R/W 1 to 8
1468h
Co-inverter
Communication Starting
Selection
C100 R/W
00: 485 terminal
01: Always started
1469h
UP/DWN Storage
Selection
C101 R/W
00: Do not store frequency
data
01: Store frequency data
5-71
146Ah Reset Selection C102 R/W
00: Trip reset at power-on
01: Trip reset at power-off
02: Enabled only during trip
(Reset when the power
is ON.)
03: Trip reset only
5-100
146Bh Reset Restart Selection C103 R/W
00: 0 Hz restart
01: Frequency matching
restart
02: Frequency pull-in restart
146Ch
UP/DWN Clear Terminal
Mode
C104 R/W
00: 0 Hz
01: EEPROM data at
power-on
5-71
146Dh
MP Gain Setting C105 R/W 50 to 200 1 [%] 5-43
146Eh AM Gain Adjustment C106 R/W 50 to 200 1 [%] 5-45
146Fh
to
1470h
Reserved −−
1471h AM Bias Setting C109 R/W 0 to 100 1 [%] 5-45
1472h Reserved −−
1473h
Overload 1 Warning
Level 2
C111 R/W 0 to 20000 0.01 [%] 5-115
1474h
to
1485h
Reserved −−
1486h
Output P1/EDM ON
Delay Time
C130 R/W 0 to 1000 0.1 [s]
5-361487h
Output P1/EDM OFF
Delay Time
C131 R/W 0 to 1000 0.1 [s]
1488h
Output P2 ON Delay
Time
C132 R/W 0 to 1000 0.1 [s]
1489h
Output P2 OFF Delay
Time
C133 R/W 0 to 1000 0.1 [s] 5-36
148Ah
to
148F
Reserved −−
1490h
Output RY ON Delay
Time
C140 R/W 0 to 1000 0.1 [s]
5-36
1491h
Output RY OFF Delay
Time
C141 R/W 0 to 1000 0.1 [s]
Register
No.
Function name
Parameter
No.
R/W
Monitor and setting
parameters
Data
resolution
Page