4-8
4-2 Function Mode
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
4
Parameter List
V/f characteristics
A244
Control Method
2
00: Constant torque
characteristics (VC)
01: Reduced torque
characteristics (VP 1.7th
power <VC, if low speed>)
02: Free V/f setting
03: Sensorless vector control
(heavy load only)
00 no no -
5-46
5-144
A045
Output Voltage
Gain 1
20. to 100. 100. yes yes %
5-72
A245
Output Voltage
Gain 2
20. to 100. 100. yes yes %
A046
Automatic
Torque Boost
Voltage
Compensation
Gain 1
0. to 255. 100. yes yes −
5-49
A246
Automatic
Torque Boost
Voltage
Compensation
Gain 2
0. to 255. 100. yes yes −
A047
Automatic
Torque Boost
Slip
Compensation
Gain 1
0. to 255. 100. yes yes −
A247
Automatic
Torque Boost
Slip
Compensation
Gain 2
0. to 255. 100. yes yes −
Parameter
No.
Function name Monitor or data range
Default
setting
Set data
Data can
be set
during
RUN
Data can be
changed
during RUN
Unit
Page