4-9
4-2 Function Mode
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
4
Parameter List
External DC injection braking
A051
Internal DC
Injection
Braking
Selection
00: Disabled
01: Enabled
02: Enabled
(Operates only on set
frequencies.)
00 yes no −
5-135
A052
Internal DC
Injection
Braking
Frequency
0.00 to 60.00 0.50 no yes Hz
A053
DC Injection
Braking Delay
Time
0.0 to 5.0 0.0 no yes s
A054
DC Injection
Braking Power
0. to 100./70.
(heavy load/light load)
50 no yes %
A055
DC Injection
Braking Time
0.0 to 60.0 0.5 no yes s
A056
DC Injection
Braking Edge/
Level Selection
00: Edge operation
01: Level operation
01 no yes −
A057
Startup DC
Injection
Braking Power
0. to 100./70. (heavy load/light
load)
0. no yes %
External DC injection braking
A058
Startup Internal
DC Injection
Braking Time
0.0 to 60.0 0.0 no yes s
5-135
A059
DC Injection
Braking Carrier
Frequency
2.0 to 15.0/10.0
(heavy load/light load or high
frequency )
5.0/2.0 no yes
kHz
Parameter
No.
Function name Monitor or data range
Default
setting
Set data
Data can
be set
during
RUN
Data can be
changed
during RUN
Unit
Page