4-16
4-2 Function Mode
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
4
Parameter List
Momentary power interruption/Trip restart
b001 Retry Selection
00: Trip
01: 0 Hz restart
02: Frequency matching
restart
03: Trip after frequency
matching deceleration
stop
04: Frequency pull-in restart
00 no yes
5-96
b002
Allowable
Momentary
Power
Interruption
Time
0.3 to 25.0 1.0 no yes s
b003
Restart
Standby Time
0.3 to 100.0 1.0 no yes s
5-96
5-100
5-103
Parameter
No.
Function name Monitor or data range
Default
setting
Set data
Data can
be set
during
RUN
Data can be
changed
during RUN
Unit