4-17
4-2 Function Mode
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
4
Parameter List
Parameter
No.
Function name Monitor or data range
Default
setting
Set data
Data can
be set
during
RUN
Data can be
changed
during RUN
Unit
Page
Momentary power interruption/Trip restart
b004
Momentary Power
Interruption/
Undervoltage Trip
During Stop
Selection
00: Disabled
01: Enabled
02: Disabled during stop and
deceleration stop
00 no yes
5-96
b005
Restart During
Momentary
Power
Interruption
Count Selection
00: 16 times
01: Unlimited
00 no yes
b007
Frequency
Matching Lower
Limit
Frequency
Setting
0.00 to 99.99
100.0 to 400.0 (1000.)
0.00 no yes Hz
5-97
5-100
5-103
b008
Overvoltage/
Overcurrent
Restart
Selection
00: Trip
01: 0 Hz restart
02: Frequency matching
restart
03: Trip after frequency
matching deceleration
stop
04: Frequency pull-in restart
00 no yes
5-97
b010
Overvoltage/
Overcurrent
Restart Count
Selection
1 to 3 3 no yes
Time
b011
Overvoltage/
Overcurrent
Restart
Standby Time
0.3 to 100.0 1.0 no yes s
Electronic Thermal
b012
Electronic
Thermal Level 1
0.20 × Rated current to 1.00 ×
Rated current
Inverter
rated
current
no yes
A
5-110
b212
Electronic
Thermal Level 2
Inverter
rated
current
no yes
b013
Electronic
Thermal
Characteristics
Selection 1
00: Reduced torque
characteristics
01: Constant torque
characteristics
02: Free setting
01 no yes
b213
Electronic
Thermal
Characteristics
Selection 2
01 no yes